Step 1: Investigate the Issue

Begin by identifying the category of failure. Is it a Power Failure or a Cooling Issue?


 Power Failure

 

1. Check Breakers:

 

 1.1 Locate the breaker panel in the restaurant. Identify the breaker labelled for the cooler/freezer.

 1.1.1  Perform the following Steps

  • Turn the breaker switch completely to the “OFF” position.
  • Wait 10-15 seconds, then flip it back to the “ON” position.
  • Observe if the unit powers up.

 

If the breaker trips again:

  • Note the frequency of tripping (it could indicate an overload or a short circuit).
  • Do not reset repeatedly. Report this to the maintenance team.

 

2. Check Power Button and Connections:

 

  • Inspect the power cord for signs of wear, fraying, or damage.
  • Confirm the plug is securely connected to a working outlet.

 

 2.1 Perform the following troubleshooting steps

  • Unplug the unit, wait for 30 seconds, and plug it back in.
  • Press the reset button if the outlet has a reset switch (GFCI).

        If no power is restored:

  • Test the outlet with another device (like a phone charger).
  • If the outlet is not working, report an electrical issue to your maintenance team.

 

Cooling issue

 

3. Low Temperature

 

3.1. Check the Thermostat Settings

  • Verify that the thermostat is set to the correct temperature.
    • Fix: Adjust the thermostat to the desired temperature.

3.1.1 Inspect the Thermostat for Faults

  • Is the thermostat stuck or showing incorrect readings?
    • Fix: Replace the thermostat if it’s faulty.

3.2 Check the Evaporator Coil for Freezing

  • Look for ice buildup on the evaporator coil.
    • Fix: Turn off the cooler/freezer and allow it to defrost.
    • Check for airflow blockages caused by ice or improper stacking of goods.
    • it can look something like this or there can be much more frost buildup

3.3. Inspect the Door Seal

  • A loose or damaged door gasket may let in cold air, causing overcooling.
    • Fix: Repair or replace the door seal if it’s not airtight.

3.4. Monitor the Defrost Cycle

  • The unit may be stuck in a cooling mode without proper defrosting.
    • Fix: Verify the defrost timer is functioning and adjust or replace it if needed.

 

4. High Temperature

 

1. Check the Thermostat

  • Verify the thermostat is set to the desired temperature.
    • Fix: Adjust the setting if incorrect.
  • Inspect the thermostat for faults or inaccurate readings.
    • Fix: Replace the thermostat if it doesn’t respond or shows incorrect temperatures.
1.1 Clean Dust from Coils
  • Locate the condenser coils (usually outside the unit).
    • Are they dusty or blocked?
      • Fix: Use a soft brush or vacuum to clean the coils gently. This improves cooling efficiency.

2. Check for Ice Buildup

  • Open the unit and inspect the evaporator coil for frost or ice accumulation.
    • Fix: Ice buildup restricts airflow and cooling.
2.1 Check Door Gasket and Openings
  • Examine the door gasket for cracks, tears, or gaps.
    • Fix: Replace or repair damaged gaskets to prevent warm air from entering.
  • Ensure the door is closed correctly and not being left open unnecessarily.
2.2 Power Off and Defrost Ice
  • If ice is present:
    • Turn off the cooler/freezer.
    • Open the door and allow the ice to melt naturally or use a defrost heater.
      • Fix: Restart the unit after the ice has melted completely.

3. Unusual Sounds or Smells

  • Listen for any strange noises from the compressor or fans, such as buzzing, grinding, or clicking.
    • Fix: These could indicate motor or fan failure. Call a technician for repair or replacement.
  • Check for burnt or chemical smells.
    • Fix: This could signify electrical issues or refrigerant leaks. Immediately power off the unit and call a technician.

 Electrical Issues in Walk-in Cooler 

  1. Power Supply Issues
  2. Thermostat Malfunction
  3. Compressor Electrical Issues
  4. Fan Motor and Condenser Fan Problems
  5. Lighting Problems
  6. Defrost Timer or Heater Issues
  7. Overloaded Circuit 

1-  POWER SUPPLY ISSUES: 

 If the cooler fails to power on or frequently shuts off, this could indicate issues in the main power supply, such as a tripped breaker, blown fuse, or damaged wiring.

     Solutions:

  •          -  Locate the circuit breaker panel and look for the switch connected to the walk-in cooler. If it’s tripped, reset it.
  •          - If fuses are present, check if any have blown then we need the Technician for this.
  •          - Look for frays or other visible damage on the power cord and plug. Open the control panel and carefully check each wiring connection. Tighten any loose ones to ensure stable power delivery.      

2-  THERMOSTAT MALFUNCTION:

An inaccurate thermostat can cause improper temperature regulation. This may lead to either insufficient cooling or the cooler freezing up.

  •          - Monitor the cooler’s temperature. If it’s consistently inaccurate, the thermostat might be faulty.
  •          -  Loose connections at the thermostat can also cause it to misread temperatures.

     Solution:

  •          - Disconnect power to prevent shock.
  •          - Remove the thermostat cover and test for loose connections, tightening as necessary.
  •          - If the thermostat cannot be recalibrated, replace it with a compatible unit.

3- Compressor Electrical Issues:

  •       1-  The compressor isn’t running, or it every now and then. The compressor clicks but doesn’t start, or it hums but doesn’t run. These components are typically housed near or on the compressor unit.

Solution:

  • Ensure the breaker supplying power to the cooler is not tripped.Open the electrical control box and check for loose wires or signs of wear, such as fraying or discoloration. Tighten any loose wiring and replace any damaged cables. Replace the capacitor if it shows signs of damage or fails the continuity test. Replace the relay if it’s faulty. Ensure any replacement parts match the original specifications.

 

  •      2-  The compressor feels extremely hot to the touch, shuts down frequently, or short cycles (turns on and off repeatedly)

Solution:

  • Clean the condenser coils with a soft brush or compressed air to remove dust and debris. Replace or repair the condenser fan if it’s not running properly. Ensure that the compressor has enough space around it for air circulation. 

 

  •      3-   Unusual sounds, such as banging, rattling, or hissing, are coming from the compressor.

Solution:

  • Tighten or replace loose mounts. If the noise persists and internal parts are damaged, replacing the compressor may be necessary. For this, consult a licensed HVAC technician.

  

  1. Fan Motor and Condenser Fan Problems:

    1-  The condenser fan dissipates heat. Electrical issues in the fan can prevent proper cooling, causing the cooler’s temperature to rise.

Solution:

  • Disconnect power before handling the fan. Carefully clean the fan blades and remove any debris buildup.

 

    2-  Dust and debris can slow the fan down or cause it to stop entirely. If the motor won’t start, the capacitor may need replacement.

Solution:

  • Test the motor’s capacitor with a multimeter, replacing it if necessary. Replace the fan motor if it’s not receiving power or fails to run despite a functioning capacitor.

 

  1. Lighting Problems:

      1-  Lights that flicker or won’t turn on may be caused by a burned-out bulb, faulty switch, or loose wiring. 

       2-  Test the light switch with a multimeter to see if it’s functional. Loose wiring near the light fixture can lead to flickering.

   Solution for point 1:

  •  Always turn off the power before replacing bulbs or working with wiring. Replace bulbs with those rated for walk-in coolers. If the switch is faulty, install a new one.

   Solution for point 2:

  •  Check and tighten any loose connections near the light fixture.

 

  1. Defrost Timer or Heater Issues:

      Excessive frost buildup or inability to maintain temperature can indicate defrost timer or heater issues.

    1-  Listen for ticking sounds from the timer. Silence may indicate it’s not functioning.

    2-  Use a multimeter to check for continuity in the defrost heater.

      Solution for point 1: 

  • Turn off the power to the cooler before inspecting the defrost timer or heater. If the timer is not operating, replace it with a compatible model.

 

     Solution for point 2: 

  • Turn off the power to the cooler before inspecting the defrost timer or heater. If the heater shows no continuity, replace it. Recheck after installation to confirm that defrost cycles are functioning.
  1. Overloaded Circuit:
  •         A walk-in cooler connected to an overloaded circuit can cause frequent breaker trips or impact the function of other devices sharing the circuit.
  •        1-  Frequent breaker trips or power loss indicate a potential overload.  
  •        2-  Confirm if other devices share the same circuit as the cooler.

 

   Solution for point 1: 

  • Work with a qualified electrician to install a dedicated line to the cooler if it shares a circuit.

 

   Solution for point 2: 

  • If the breaker is undersized, upgrade to a higher amperage that matches the cooler’s power needs.

 

 

How to Clean the Cooler Filter

 

  • Turn off the power
  • use a soft brush and clean the coil filter in a vertical manner
  • after cleaning, place a water container beneath the filter and use some clean water and coil cleaner spray, check the video for more details

 

 



  • General Safety Guidelines:
  • Always Disconnect Power: Turn off the main power before inspecting or repairing any electrical components.
  • Use Insulated Tools: Prevents accidental shock.
  • Wear Personal Protective Equipment (PPE): Gloves, goggles, and long sleeves add protection.
  • Use a Voltage Tester: Verify no live current is present before touching any wiring or components.
  • Seek Professional Help for Complex Issues: If electrical issues persist, consult a qualified electrician.

Contact Our Team